PVC sheathed XLPE insulated power cables for nominal voltage up to 1kV. The cables meet the requirements of Specs. 16.К71-277-98.
The cables are intended for power transmission and distribution in stationary equipment for nominal voltage 1kV, nominal frequency 50Hz.in power systems with insulated and grounded neutral.
The primary scope of application: for single-laying of cable lines in cable installations, indoor if there is no danger of mechanical damage while operating.
Flame-retardant while single laying.
Fire safety class - 01.7.2.3. according to NPB 248-97 classification.
Type of climatization: B, allocation category 5 as per national standard GOST 15150-69.
| The operating temperature range | -50°С to +50°С |
| Continuously permissible conductor operating heating temperature | no more than +90°С |
| Short circuit conductor max. temperature | no more than +250°С |
| Permissible conductor operating heating temperature under overload condition, ≤ | +130°С |
| Face-to-face length for main conductor areas |
|
| Cable Installation and assembly without preheating | Not lower -15°С |
| Bending radius when laid: | 7,5 outer cable diameters |
| Guaranty service life | 5 years from the date of commissioning, but not later than 6 months from the date of manufacturing. |
| Service life | not less than 30 years |