PVC insulated and sheathed, flame retardant, low smoke, screened control cables. The cables meet the requirements of Specs. 16.К71-310-2001.
The cables are designed for fixed connection to electric devices, machines and assemblies of electric distribution devices for alternating voltage up to 660 V and frequency up to 100Hz.or for fixed voltage up to 1kV.
The cables are produced for industrial application and application in nuclear power stations by deliveries to home and export markets.
The cabels are designed for use in cable structures and areas, including nuclear power systems, class 3 or 4 as per classification ОПБ-88 (ПНАЭ Г-01-011-97).
The cables are flame-retardent while bundled installation.
Class of fire safety on classification НБП 248 - П1.7.2.1.
Type of climatization: UHL, allocation category 1 and 5 as per national standard GOST 15150-69, .
| Operating temperature range (relative air humidity at the temperature up to +35°С-up to 98%) | -50°С to +50°С |
| Permissible conductor operating heating temperature | +70°С |
| Max flame-retardant cable conductor temperature in case of short-circuit | +400°С |
| Face-to-face length | at least 150 m |
| Cable Installation and assembly without preheating | not lower -15°С |
| Bending radius of cable while installation and assembly | not less than 6 outer cable diameters |
| Bending radius of cable when laid at ambient temperature not lower 0°С should be: |
|
| Service life while installation in buildings, channels, tunnels |
|
| Guaranty service life | 3 years from the date of commissioning, but not later than 6 months from the date of manufacturing. |