КВВГЭнг-LS

PVC insulated and sheathed, flame retardant, low smoke, screened control cables. The cables meet the requirements of Specs. 16.К71-310-2001.

Structure

  1. Conductor — copper, single. Class 1 as per national standard GOST 22483-77.The number of conductors: 4-61.
  2. Insulation — low flammability PVC composition.
  3. Stranding — insulated solid circular conductors are stranded to form a core. Each layer has a marker pair, its insulated conductors carry identification coloring and differ from the other conductors.
  4. Isolator — low flammability PVC composition.
  5. Screen — winding of an aluminium foil with copper applied along the screen. Upon request — winding of copper foil.
  6. Sheath — low flammability PVC composition is applied over the screen.

Аpplication

The cables are designed for fixed connection to electric devices, machines and assemblies of electric distribution devices for alternating voltage up to 660 V and frequency up to 100Hz.or for fixed voltage up to 1kV.

The cables are produced for industrial application and application in nuclear power stations by deliveries to home and export markets.

The cabels are designed for use in cable structures and areas, including nuclear power systems, class 3 or 4 as per classification ОПБ-88 (ПНАЭ Г-01-011-97).

The cables are flame-retardent while bundled installation.

Class of fire safety on classification НБП 248 - П1.7.2.1.

Specifications

Type of climatization: UHL, allocation category 1 and 5 as per national standard GOST 15150-69, .

Operating temperature range (relative air humidity at the temperature up to +35°С-up to 98%) -50°С to +50°С
Permissible conductor operating heating temperature +70°С
Max flame-retardant cable conductor temperature in case of short-circuit +400°С
Face-to-face length at least 150 m
Cable Installation and assembly without preheating not lower -15°С
Bending radius of cable while installation and assembly not less than 6 outer cable diameters
Bending radius of cable when laid at ambient temperature not lower 0°С should be:
  • for cables with outer diameter 10 mm — 3 cable diameters
  • for cables with outer diameter 10-25 mm — 4 cable diameters
Service life while installation in buildings, channels, tunnels
  • not less than 30 years
Guaranty service life 3 years from the date of commissioning, but not later than 6 months from the date of manufacturing.